風(fēng)管的透光試驗(yàn)標(biāo)準(zhǔn)事項(xiàng)

發(fā)布人:http://www.hkcts.com.cn   發(fā)布時(shí)間:2023-06-02 14:52:42

對(duì)于風(fēng)管系統(tǒng)嚴(yán)密性檢驗(yàn)的方法有兩種:低壓系統(tǒng)的風(fēng)管在制作、安裝工藝得到保證的前提下,可采用漏光法檢驗(yàn)中、高壓系統(tǒng)風(fēng)管應(yīng)采用漏風(fēng)量測(cè)試方法。下面濟(jì)南風(fēng)管加工廠為您進(jìn)行分析:

There are two methods for inspecting the tightness of the air duct system: under the premise of ensuring the production and installation process of the low pressure system air duct, the light leakage method can be used for inspection. The medium and high pressure system air ducts should use the air leakage test method. Below, Jinan Air Pipe Processing Factory will analyze for you:

1、風(fēng)管系統(tǒng)安裝完畢后,應(yīng)按系統(tǒng)類別進(jìn)行嚴(yán)密性檢驗(yàn)。

1. After the installation of the air duct system is completed, the tightness inspection should be carried out according to the system category.

2、檢測(cè)應(yīng)采用具有一定強(qiáng)度的光源。手持移動(dòng)光源可采用不低于100W帶保護(hù)罩的低壓照明燈,或其他低壓光源。

2. The detection should use a safe light source with a certain intensity. Handheld mobile light sources can use low-voltage lighting lamps with protective covers of no less than 100W, or other low-voltage light sources.

3、系統(tǒng)風(fēng)管漏光檢測(cè)時(shí),光源可置于風(fēng)管內(nèi)側(cè)或外側(cè),但其相對(duì)側(cè)應(yīng)為暗黑環(huán)境。檢測(cè)光源應(yīng)沿著被檢測(cè)接口部位與接縫做緩慢移動(dòng),在另一側(cè)進(jìn)行觀察,當(dāng)發(fā)現(xiàn)有光線射出,則說(shuō)明查出明顯漏風(fēng)處,并應(yīng)做好記錄。

3. When detecting air duct leakage in the system, the light source can be placed on the inner or outer side of the air duct, but its opposite side should be in a dark environment. The detection light source should move slowly along the tested interface and seam, and observe on the other side. If light is found to be emitted, it indicates that a significant air leakage has been identified and records should be kept.

20220523220314.png

4、對(duì)系統(tǒng)風(fēng)管的檢測(cè),宜采用分段檢測(cè)、匯總分析的方法。在嚴(yán)格安裝質(zhì)量管理的基礎(chǔ)上,系統(tǒng)風(fēng)管的檢測(cè)以總管和干管為主。

4. The detection of system air ducts should be carried out using segmented detection and summary analysis methods. On the basis of strict installation quality management, the detection of system air ducts is mainly focused on the main and main pipes.

當(dāng)采用漏光法檢測(cè)系統(tǒng)的嚴(yán)密性時(shí),低壓系統(tǒng)風(fēng)管以每10m接縫,漏光點(diǎn)不大于2處,且100m接縫平均不大于16處為合格中壓系統(tǒng)風(fēng)管每10m接縫,漏光點(diǎn)不大于1處,且100m接縫平均不大于8處為合格。

When using the light leakage method to detect the tightness of the system, the low-pressure system air duct is qualified if there are no more than 2 light leakage points per 10m of joints, and the average number of 100 m joints is no more than 16. The medium pressure system air duct is qualified if there are no more than 1 light leakage point per 10m of joints, and the average number of 100 m joints is no more than 8.

風(fēng)管的透光試驗(yàn)標(biāo)準(zhǔn)事項(xiàng)就講解到這里了,希望能夠給您好的幫助,更多事項(xiàng)就來(lái)我們網(wǎng)站http://www.hkcts.com.cn咨詢了解吧!

That's all for the standard items on the transparency test of the air duct. I hope you can be helpful. For more information, please come to our website http://www.hkcts.com.cn Consult and understand!


上一篇:白鐵皮通風(fēng)管道加工的技術(shù)要求
下一篇:通風(fēng)管道內(nèi)風(fēng)速及風(fēng)量的測(cè)定事項(xiàng)